            简单介绍:
        
        
            Electroswitch Control Switch Relays (CSR) combine the function of a control switch with a remote controlled solenoid allowing one device to do both the manual and supervisory control function in the c
        
    
            详情介绍:
        
        
            SERIES 24 CSR
 
 
 
 
 
 
 
 
 
 
          Electroswitch Control Switch Relays (CSR) combine the function of a control switch with a remote controlled solenoid allowing one device to do both the manual and supervisory control  function in the control of power circuit breakers. They eliminate the need to redesign substa-  tions for redundant separate relays when manual substations convert to supervisory control.  CSRs provide manual or electric control switch operation by supervisory control. The CSR  looks, acts, and feels identical to a control switch.  
Note: The Series 24 CSR Class 1E utility products comply with the following NuclearC37.105, ANSI/IEEE 323, ANSI/IEEE 344, ANSI/ASME NQA -1.  
Standards: ANSI/IEEE C37.90, ANSI/IEEE C37.90.01, ANSI/IEEE C37.98, ANSI/IEEE
Series 24 Control Switch Relays
HIGH  QUALITY   in the industry  •    Designed and manufactured to the highest standards 
•    Qualified to UL, CSA, ANSI/IEEE 37.90 and 37.90 .1 
VERSATILITY       associated wiring •     Replaces a manual breaker switch, interposing relays, and 
•     Direct retrofit to existing manual breaker control switch 
•     Electric or manual operation   
•     Three circuits to satisfy different industry applications 
•     Multiple voltages: 48VDC, 125VDC, standard, others available 
•     All standard Series 24 circuit breaker control switch contacting 
•     Available with custom contacting (consult factory) 
SAFETY            •     Target flag agreement (regardless of manual or electric trip)  
•     Available with SCADA disable for operator safety during service 
•     1E Nuclear qualified 
AVAILABILITY     24 CSRs are available from stock for quick delivery. See pg.13  (Switch Section) for Series 24 Universal Circuits.   •    Virtually all Universal Circuits in standard voltages of the Series 
SERVICE •    The Electroswitch team of Customer Service and Applications   Professionals stand behind every Electroswitch product. Let us   put over 50 years of know-how to work for you!     only requires two contacts (S1 and S2) to command the CSR to either the TRIP or CLOSE  position. Low level contacts (rated 1 ampere) may be used since S1 and S2 do not control  the rotary drive solenoid directly.  
Basic Circuit Operation
The control of the CSR Control Switch Relay for electric operation requires no special wiring. It figures represents the rotary solenoid that drives the CSR. Its operation is further described  later. LS1 is a linear solenoid within the device that changes the sense of direction of the CSR  from left (TRIP) to right (CLOSE). The contacts shown as CSR are contacts within the device.  Other components are shown by conventional designations.   in the following figures is in the vertical NORMAL position. The CSR coil form shown on the
The standard station control bus voltage is used on all three circuits. The device, when shown 
Mechanical Targetturned as well (GREEN for TRIP, RED for CLOSE). The target remains latched when the handle  
returns to normal position and always shows the last active position

.jpg)
.jpg)
When the CSR Switch handle is turned, a mechanical target contained in the nameplate is
        returns to normal position and always shows the last active position

.jpg)
.jpg)
 
 
    