    - welded and soldered connections, equipotential bonding, earth wire,
- terminals and connectors, rail welded joints, cables and wires,
- measurement 4-pole method.
- Measurement of inductive object type:
 - coils (motors and transformers), low resistance coils.
- Range selection autoranging or manual (measurement of inductive object type).
- Selectable measurement mode adjusted to object type:
 - for resistive objects - fast mode (3 seconds),
 - for inductive objects - long mode with automatic discharge after measurements (or with lower accuracy - shorter mode).
- Selectable measurement mode adjusted to application:
 - normal mode - after pushing „START” button,
 - automatic mode - since test leads are connected to the object meters automatically starts measurement with dual direction current flow and gives average result - what eliminates eventual DC voltage on tested object,
 - continuous mode - every 3 seconds for resistive objects or continuous measurement for inductive objects.
- Window mode:
 - this option enables setting an upper and a lower limit between which the average measurement result is bound to appear. The results outside of this range will be indicated by two long audible signals and the symbols.
- MMR-630 is designated not to be effected by interference up to 20mV and to show noises from 20 to 100mV (so in edge conditions even 5 times higher than measured drop of potential).
- Memory store for up to 990 results and a communications facility for transferring data from the device to a PC.
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT III 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP54
Other technical data:
- meter’s power supply: battery package SONEL/Ni-MH 4,8V
- battery charging time: approx. 2,5 hours
- number of measurements with the current of 10A: 300
- auto-off time: 120 seconds
- immunity to interference: additional error ≤1% for voltage 50 Hz ≤100mV RMS
- maximum leads resistance for the 10A current: 0,1Ω
- maximum inductance of the tested object: 40H
- accuracy of the test current: ±10%
- resistance measurement time:
    - with the selected resistive object type with the bidirectional current:     3 seconds
    - with the selected inductive object type, dependant on the resistance 
      and inductance of the object:     a few minutes (max. 10)
- dimensions: 295 x 222 x 95 mm
- weight: approx. 1,7 kg
Rated operational conditions:
- operation temperature: 0...+40°C
- storage temperature: -20...+60°C
MMR-620 microohmmeter conforms the following directives 
or standards according to CE requirements.
Directive:
Low Voltage Directive (LVD) 73/23/EEC, 93/68/EEC.
Standards:    
EN 61010-1:2001 Safety requirements for electrical equipment for measurement, control and laboratory use. General requirements .
EN 61010-031:2002: Safety requirements for electrical equipment for measurement, control and laboratory use. Safety requirements for hand-held probe assemblies for electrical measurement and test.
Directive:    
Electromagnetic compatibility (EMC) 89/336/EEC, 92/31/EEC, 93/68/EEC.
Standards:
EN 61326:1997+A1:1998+A2:2001 Electrical equipment for measurement, control and laboratory use - EMC requirements.
 
Resistance measurement
| MMR-620 | Current | Voltage for the full scale | Accuracy | |
| Range | Resolution | |||
| 0...999μΩ | 1μΩ | 10A | 20mV | ±(0,25%m.v. + 2 digits) | 
| 1,000...1,999mΩ | 0,001mΩ | |||
| 2,00...19,99mΩ | 0,01mΩ | 200mV | ||
| 20,0...199,9mΩ | 0,1mΩ | 1A | ||
| 200...999mΩ | 1mΩ | 0,1A | ||
| 2,00...19,99Ω | 0,01Ω | |||
| 20,0...199,9Ω | 0,1Ω | 1mA | ||
| 200...1999Ω | 1Ω | 0,1mA | ||
- input impedance of the voltmeter: ≥200kΩ
„m.v.” - measured value.
 
 
    