| | Introduction: |  | It is a Phase Failure with Under & Over Voltage Relay. It is best suitable for protection of balanced 3 phase loads or 3 phase Motor / Pump loads only or for monitoring 3 phase MAINS supply. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in 11 pin Plug-in base mounting & flash mounting enclosure. | 
 | 
|  | 
| | | Features: |  | · Under & Over Voltage (Factory Set). · Monitors Aux.Voltage for Under & Over Voltage.
 · Monitors all 3 phases of voltage for unbalance & phase loss.
 · Built-in Aux.Voltage.
 · Auto Reset.
 · Panel Flush Mounted Enclosure.
 
 | 
 |  |  | 
 | 
|  | 
| | Application Areas: |  | Measures 3-Phase supply for Unbalance Voltage, Loss of Phase, Phase Sequence, Under Voltage & Over Voltage. Best suitable for balance 3 phase loads or motor loads only. Phase failure &UV/OV Relays can be best used for a host of Auxiliary Systems & Plant control panels & machinery. | 
 | 
|  | 
| Technical Specifications: | 
|  | 
| |  |  | Specifications |  | 1 | Supply Voltage | System240 / 380 / 400 / 415 V AC ± 20%, 50 / 60 Hz; Auxiliary Built-in |  | 2 | Output Contacts | 1 CO |  | 3 | Trip Setting (Volts) | Phase unbalance 40 V ± 6 V (fixed); Under Voltage 190 V (fixed); Over Voltage 260 V (fixed); Water Level N.A. |  | 4 | Trip Time Delay | On Phase Failure 3.5 secs ± 1.5 sec.; On UV/OV 10 secs. |  | 5 | Resetting Mode |  |  | 6 | Weight | 430 gms. |  | 7 | Dimensions (mm) | Overall (L x W x D) 96 x 96 x 76 (flush mounting); Mounting (L x W) 92 x 92 (cutout) | 
 |