| | Introduction: |  | It is a compact version of SP D2. It senses the Negative Sequence Voltage components of the system supply & offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal. The user can set the unbalance voltage as per field requirements & optimally use the motors. It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Motor Control Panels. It is available in DIN Rail mounting enclosure. | 
 | 
|  | 
| | | Features: |  | · Monitors 3 Phase Voltage Supply. · Suitable for any System Voltage
 · Manual / Remote /Auto Reset (Selectable)
 · Fault Trip Indications (LED’s)
 · 2 CO output contacts 2 CO output contacts
 · Sleek DIN Rail mounted D1 Enclosure.
 
 | 
 |  |  | 
 | 
|  | 
| | Application Areas: |  | It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Motor Control Panels. It is available in DIN Rail mounting enclosure. | 
 | 
|  | 
| Technical Specifications: | 
|  | 
| |  |  | Specifications |  | 1 | Supply Voltage | System 240 / 380 / 415 V AC ±20%; Auxiliary 110 / 240 / 380 / 415 V AC ±20% |  | 2 | Output Contacts | 1 CO |  | 3 | Trip Setting (Volts) | Phase unbalance 30 to 70 V ±6 V (adjustable); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A. |  | 4 | Trip Time Delay | On Phase Failure/Seq. 3.5 sec. ±1.5 sec. |  | 5 | Resetting Mode | Auto |  | 6 | Weight | 320 gms. |  | 7 | Dimensions (mm) | Overall (L x W x D) 78 x 30.5 x 117.5; Mounting (L x W) 68 centre to centre | 
 |