| | Introduction: |  | Measures & scans 3 phase voltage supply and display the line voltage or Line to Neutral Voltage. It also monitors the Under & Over voltage conditions & compare with the Programmed Preset trip levels. In case, it exceeds the preset limits it de-energizes an output relay. The Scanners can be Manually reset. | 
 | 
|  | 
| | | Features: |  | · Digital 3 phase voltage readout. · Scan time of 5 sec each
 · Preset under voltage trip( 75% - 95%) adjustable.
 · Preset over voltage trip( 105% - 120% ) adjustable.
 · Energizing time delay( 2- 5 sec)
 · 1 CO( 2 CO) output relay rated 5A/230V AC.
 · Manual reset
 · DIN panel cutout flush mounted enclosure.
 
 | 
 |  |  | 
 | 
|  | 
| | Application Areas: |  | Generator panels AMF controls panels UPS control panels Power distribution panel | 
 | 
|  | 
| Technical Specifications: | 
|  | 
| |  |  | Specifications |  | 1 | Supply voltage | System 3 Phase 380 / 415 / 440 V AC±30%; Auxillary 110 / 240 / 380 / 415 / 440 V AC / 24 V DC +20%, -25% |  | 2 | Output relay contacts | 1 CO (2 CO) |  | 3 | Trip setting | Under Voltage 75% - 95% of monitored supply; Over Voltage 105% - 120% of monitored supply |  | 4 | Trip time delay | 3.5 secs ± 1.5 secs |  | 5 | Reset | Auto / Manual |  | 6 | Display | 3 digit, with 1 V resolution & 4 - 7 Secs Scan time |  | 7 | Monitoring | Phase to Phase |  | 8 | Weight | 1100 gms. |  | 9 | Dimensions (mm) | Overall (L x W x D) 144 x 72 x 205; Mounting (L x W) 138 x 66 | 
 |