  • 产品名称:PD6830系列5位隔爆型脉冲输入流量积算仪 (回路供电)

  • 产品型号:PD6830
  • 产品厂商:PRECISION
  • 产品价格:0
  • 折扣价格:0
  • 产品文档:
你添加了1件商品 查看购物车
简单介绍:
Pulse, Open Collector, NPN, PNP, TTL, Switch Contact, Sine Wave (Coil), Square Wave, Opto-Isolated Inputs Isolated 4-20 mA Output for Rate or Total 5-Digit Rate, 0.7" (17.8 mm) 7 Alphanumeric Chara
详情介绍:
PD6830 ProtEX-RT PD6830 PULSE INPUT RATE/TOTALIZER ProtEX-One Logo

FEATURES

  • Pulse, Open Collector, NPN, PNP, TTL, Switch Contact,
    Sine Wave (Coil), Square Wave, Opto-Isolated Inputs
     
  • Isolated 4-20 mA Output for Rate or Total
     
  • 5-Digit Rate, 0.7" (17.8 mm)
     
  • 7 Alphanumeric Character Total/Tag, 0.4" (10.2 mm)
     
  • Battery, DC, or Output Loop-Powered Models
     
  • Gate Function for Rate Display of Slow Pulse Rates
     
  • SafeTouch™ Through-Glass Button Programming
     
  • K-Factor, Scaling, or Live Input Calibration
     
  • Explosion-Proof, IP68, NEMA 4X Enclosure
     
  • Flanges for Wall or Pipe Mounting
     
  • Password Protection
     
  • Battery, DC, and Output Loop-Powered Backlight Models
     
  • Operates from -40 to 75°C, (-20 to 75°C on Battery Models)
Hazardous Area Approvals for PD663 ProTex
 

OVERVIEW

The ProtEX-RT PD6830 is a rugged, explosion-proof pulse input rate/ totalizer fully featured for demanding applications in hazardous areas or in the harshest environmental conditions. It is programmed using the four SafeTouch™ through-glass buttons, without removing the cover. The numeric rate display will read up to 99999 and the alphanumeric total/tag display will read up to 9999999. The alphanumeric display can also be programmed to show any combination of numbers and letters up to seven characters long for use as engineering units and/or the process identification tag. The backlight makes the display visible under any lighting condition. The enclosure is provided with threaded conduit holes and integrated pipe or wall mounting slotted flanges.

PD6830 with callouts

KEY FEATURES

User Friendly Display

The high contrast 0.7" high 5-digit LCD on the upper display is easy to read. The 0.4" 7-character lower display is alphanumeric and allows for more sensible looking tags, engineering units, or legends than a 7-segment display. For dark areas, the backlight (standard) can be illuminated either via output loop power (BTA & CTB), external 9 to 30 VDC (APO & APA), or battery (BMO).

Through-Glass SafeTouch™ Buttons

PD6820 Safe TouchThe PD6830 is equipped with four sensors that operate as through-glass buttons so that it can be programmed and operated without removing the cover (and exposing the electronics) in a hazardous area. These buttons can be disabled for security by selecting the LOCK setting on the switch located on the connector board in the base of the enclosure. To actuate a button, press one finger to the glass directly over the marked button area. When the cover is removed, four mechanical buttons located next to the sensors are used.

Exceptional Enclosure

PD6830 Wide Viewing Angle
Wide Viewing Angle

The copper-free (0.3%), smooth cast aluminum NEMA 4X enclosure is finished with a corrosion resistant epoxy coating. This provides a durable finish, and helps make it an attractive looking enclosure. The built-in mounting flanges are convenient for wall or pipe mounting (up to 2½" pipes). The enclosure is provided with three ¾" NPT threaded conduit holes. The window and display module on the PD6830 enclosure have been optimized to provide a wide viewing angle of approximately +/- 40°, nearly twice the competition! This makes it even easier for operators to see the display.

Environmentally Tough

PD6830 Environmentally Tough

 

Alarm Indication

The PD6830 can be configured to have a high or low rate alarm indicator, or a total alarm set point indicator. When in alarm mode, the display will flash, and a HI or LO symbol is displayed. The alarm is acknowledged by pressing the ENTER/ACK button.
PD6830 Alarm Indication



PD6830 ProTEX RT Wide Input Signal SelectionWide Input Signal Selection


Wide Input Signal Selection

The PD6830 is designed to handle a wide variety
of inputs, including: pulse, open collector, NPN,
PNP, TTL, or switch contact. The input can handle
up to a 30 kHz signal without degradation. It can
readily discern inputs with pulse widths as small
as 16 µs. Inputs are conveniently set up on the
display module by simply moving switches to the
desired options.





Gate Function for Slow Pulses

The gate function provides for rate display of slow pulse rates. Using the programmable gate, the meter is able to display pulse rates as slow as 1 pulse every 999 seconds (0.001 Hz). The gate function can also be used to obtain a steady display reading with a fluctuating input signal. There are two settings for the Gate, low gate () and high gate ().

Totalizer Conversion Factor

Total Conversion Factor is used to convert to a different unit of measure for the total display. For example, to display rate in gallons and total in liters, enter a Conversion Factor of 3.7854. When rate and total units are the same, the Conversion Factor should be 1.0000.
PD6830 Totalizer Conversion Factor
 


Password Protection

A 5-digit password prevents unauthorized changes to the programmed parameter settings. The lock symbol is displayed to show that settings are protected. If the meter is password protected, the meter will display the message LOCKED when the Menu button is pressed.
PD6830 Password Protection
 


K-Factor Scaling

The meter may be scaled using the K-Factor function. Most flowmeter manufacturers provide this information with the device. Enter the K-Factor () menu and select the decimal point with highest resolution possible and program the K-Factor value (i.e. pulses/gal). The meter will automatically calculate the flow rate using the K-Factor and the time base selected.

Custom Meter Scaling

In lieu of K-Factor scaling, the meter can be scaled to any span relative to the input pulse rate span (i.e. if you knew the pulse input span for gallons but wanted to display the rate and total in liters). No external signal is required.

Field Calibration with Scaling

In lieu of K-Factor and Meter Scaling, the meter can be calibrated with a precision signal source. While applying a precision signal, the relative scale value is entered via the front panel. This is done at any two points along the scale. Using this method, an operator can set a "best fit straight line" for non-linear input spans.

Alternating Total/Tag Display

The meter can be configured so that the lower display automatically toggles between displaying the assigned tag name and total every 10 seconds.
PD6830 Displaying Total
PD6830 Displaying Total

PD6830 Displaying Tag Name
PD6830 Displaying Tag Name


Design Simplicity

The internal cast rails within the enclosure replace fragile standoffs. They also guide and mount the internal module. Two springloaded thumbscrews make the assembly a snap, while pressing the LCD as close as possible to the glass window to improve wide-angle viewing.
PD6830 Design Simplicity


Pulse to 4-20 mA Retransmission

Use the analog output to retransmit the pulse input signal to the commonly used 4-20 mA form. Available on the PD6830's ATA, BTA, and CTB models. Output can be scaled to represent all, or part, of the actual input span. Shown below with switch contact input on a PD6830-APA. See manual for details.
PD6830 Pulse to 4-20 mA Retransmission>


PD6830 Two-Point Linearizer Function



Multi-Point Linearizer

The PD6830 has a linearizer which can be
assigned to any two points within the input
function range for best fit. The scale will follow
the linearization slope to the limits of the pulse
frequency input.

PD6830 minimizes linearity error by "best" fitting
a straight line to a non-linear curve.






INSTALLATION

Direct Mounting

The PD6830 is designed to easily mount directly to a flowmeter. The example below shows it mounted to a turbine flowmeter. This particular ProtEX model (BMO) is battery-powered. Even though battery-powered, it does have a backlight; but to conserve battery power, it only turns on while SafeTouch™ buttons are in use.
PD6830 Direct Mounting Installation


Installation Flexibility

The PD6830's rotatable display/meter along with three available conduit connections provide for numerous installation options. The display can be rotated in 90° increments. Rotate it 90° for horizontal mounting. Wiring can be routed to the most convenient conduit connection(s). One metal conduit plug is supplied per unit. Additional plugs are available (PDA75PLUG) if needed.
PD6830 Installation Flexibility

Easy Wiring & Service

It is simple to completely remove the meter module, and set it aside. A heavy duty terminal block is then easily accessed. It is clearly marked to prevent wiring errors. Since the meter module can be removed without breaking the loop, it can be serviced without the need to uninstall the entire product.

PD6830 Easy Wiring & Service

FLEXI-POWERED

There are ProtEX-RT models that can be powered by battery, DC with battery back-up, DC only, or the output-loop. Under nominal battery operating conditions, the battery life is approximately 5 years. As an unused back-up, the life is the shelf-life of the battery (up to 20 years). When powering the PD6830-CTB by the output loop, the output load impedance must not exceed 700 O @ 24 VDC excitation (more in specifications).

CONNECTIONS

To access the wiring connections, remove the enclosure cover and unscrew the two captive screws that fasten the display module. Disconnect the ribbon cable and remove the display module. Power and signal connections are made to a terminal block at the base of the enclosure. Grounding connections are made to the two ground screws provided on the base — one internal and one external.
PD6830 Connection Diagram

Model Power
PD6830-BM0 Battery (or DC) Powered*
PD6830-BTA Battery (or DC) Powered*
PD6830-AP0 DC Powered
PD6830-APA DC Powered
PD6830-CTB Output Loop Powered
* When DC powered, battery will provide
backup power when DC power is lost.


 
Battery, only for models:
PD6830-BM0 & PD6830-BTA
 


 
Not present on models:
PD6830-BM0 & PD6830-AP0
 


 
Not present on model:
PD6830-CTB
Code Description
ISO+ Isolated signal input positive terminal connection.
ISO- Isolated signal return/negative terminal connection.
S+ Signal input positive terminal connection.
S- Magnetic pickup (coil) signal return/negative terminal connection.
COM Signal return/negative, DC power return/negative, Contact closure reset return/negative terminal connection.
RST+ Contact closure reset pullup to 3 VDC.
P+ DC Power positive terminal connection.
LP+ 4-20 mA transmitter DC power positive terminal connection.
LP- 4-20 mA transmitter regulated current output terminal connection.

DIMENSIONS

PD6830 Mounting Dimensions

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.

General

Display: Five digits (-9999 to 99999) 0.70" (17.8 mm) high, 7-segment, automatic lead zero blanking. Seven characters (Alphanumeric Engineering Units) 0.4" (10.2 mm) high, 14 segment. Symbols: HI, LO, & SET Alarm, Password Lock.
Backlight: White LED, 10 sec auto-off for battery powered models.
Display Update Rate: Ambient > -25°C: 2 Updates/Second. Ambient < -25°C: 1 Update/5 Seconds
Overrange: Display flashes 99999
Underrange: Display flashes -9999
Programming Method: Four SafeTouch™ through-glass buttons when cover is installed. Four internal pushbuttons when cover is removed.
Recalibration: Calibrated at the factory to read frequency in Hz. No recalibration required.
Max/Min Display: Max/Min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password: Programmable password restricts modification of programmed settings and manual total reset via button interface.
Alarm Indication: Flashing display plus HI/LO indicators
Non-Volatile Memory: All programmed settings and total are stored in non-volatile memory for a minimum of ten years if power is lost.
Power Options: 9-30 VDC, 2.2 W max, 4-20 mA transmitter output power, 30 VDC max, battery power, or DC power with battery backup.
Battery: 3.6 V Primary Lithium (Li-SOCl2), non-rechargeable. Expected service life is 5 years. Recommended replacement interval: 3 years when exclusive source, up to 20 years in backup configuration. Model PDABAT36D.
Isolation: All models: 500 V opto-isolated input-to-power/output.
   PD6830-BTA: 500 V input-to-output.
   PD6830-APA: 500 V input/power-to-output
Note: Requires separate output supply
Operating Temperature Range: -40 to 75°C. (-20 to 75°C on battery powered models).
Storage Temperature Range: -40 to 75°C.
Relative Humidity: 0 to 90% non-condensing
Connections: Screw terminals accept 12 to 22 AWG wire
Enclosure: Explosion-proof die-cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Copper-free (0.3%). Three ¾" NPT threaded conduit openings. One ¾" NPT metal plug with 12 mm hex key fitting installed.
Mounting: May be mounted directly to conduit. Two slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting.
Overall Dimensions: 5.65" x 5.25" x 4.86" (W x H x D) 144 mm x 133 mm x 124 mm)
Weight: 5.00 lbs (80 oz, 2.27 kg)
Warranty: 3 years parts and labor

Rate Input

Pulse Input: Field selectable; Sourcing or sinking pulse or square wave 0-5V, 0-12 V, or 0-24 V; TTL; NPN or PNP transistor; Open collector 100k Ω pull-up to 3 V; Switch contact 100k Ω pull-up to 3 V; PNP transistor 100k Ω pull-down to ground (COM). Maximum Frequency: 30 kHz. Minimum Pulse Width: 16 µs
Opto-Isolated Input: Sourcing pulse or square wave 0-5 V, 0-12 V, or 0-24 V; Logic High: 4-30 V, Logic Low: < 1 V. Maximum Frequency: 10 kHz Minimum Pulse Width: 50 µs. Input Current: 1 mA @ 5 V, 2.5 mA @ 12 V, 5 mA @ 24 V
Low Voltage Mag Pickup Input: Sensitivity: 40 mVp-p to 24 Vp-p.
Maximum Frequency: 30 kHz
Minimum Input Frequency: 0.001 Hz. Minimum frequency is dependent on high gate setting.
Input Impedance: Pulse input: Greater than 300k Ω @ 1 kHz.
Open collector/switch input: 100k Ω pull-up to 3 V.
Accuracy: ±0.03% of calibrated span ± count
Temperature Drift: Rate display is not affected by changes in temperature.
Low-Flow Cutoff: 0-99999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration: May be calibrated using K-Factor, scale without signal source, or by applying an external calibration signal.
K-Factor: Field programmable K-Factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 9999999 pulses/unit.
Calibration Range: Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span is 10 Hz. An error message will appear if the input 1 and input 2 signals are too close together.
Contact Debounce Filter: Select low speed: 40 Hz maximum input frequency
Time Base: Second, minute, hour, or day
Gate: Low gate: 1-99 seconds; High gate: 2-999 seconds

Rate/Totalizer

Display Assignment: The Top display is assigned to rate. The Bottom display is programmable to alternate between total for 10 seconds, then the tag for 2 seconds or to show only the total or to show only the tag.
Total Decimal Point: Up to six decimal places or none: d.dddddd, d.ddddd, d.dddd, d.ddd, d.dd, d.d or ddddddd. Total decimal point is independent of rate decimal point.
Totalizer: Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed.
Total Reset: Via SafeTouch™ RESET button, mechanical button (cover off), external contact closure, or automatically via user selectable preset value and time delay. Manual reset may be disabled or protected by password.
Totalizer Rollover: Totalizer rolls over when display exceeds 9,999,999

4-20 mA Transmitter Output

Output Source: Rate/process or total
Scaling Range: 4.000 to 20.000 mA for any display range.
Calibration: Factory calibrated: 0.0 to 1000.0 = 4-20 mA output
Underrange: 3.8 mA
Overrange: 20.5 mA
Accuracy: ±0.1% FS ±0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
External Loop Power Supply: 30 VDC maximum
Output Loop Resistance:
Voltage Range Minimum
24 VDC 10 Ω 700 Ω
30 VDC 100 Ω 1200 Ω


Product Ratings & Approvals

FM: Explosion-proof for use in Class I, Division 1, Groups B, C, D. Class II, Division 1, Groups E, F, G. Class III, Division 1; T6. Class I, Zone 1, AExd IIC T6 Gb. Zone 21, AEx tb IIIC T85°C. Ta = -40 to 75°C.
Enclosure: Type 4X & IP66. Certificate number: 3040391
ATEX: II 2 G D. Ex d IIC T6 Gb. Ex tb IIIC T85°C Db IP68. Ta = -40 to 75°C. Certificate number: Sira 10ATEX1116X
IECEx: IECEx SIR 10.0056X. Ex d IIC T6 Gb. Ex tb IIIC T85°C Db IP68.Ta = -40°C to +75°C
CSA: Enclosure: Type 4X & IP66. Class I, Division 1, Groups B, C, D. Class II, Division 1, Groups E, F, G. Class III, Division 1; T6 Class I, Zone 1, Ex d IIC T6. Ta = -40°C to +75°C Certificate number: 11 2325749
 

ORDERING INFORMATION

Products

Model Description  
PD6830-BM0        Dual-Line Explosion-Proof Rate/Totalizer Pulse Input + Backlight; Powered from Battery and 9-30 VDC         
PD6830-BTA        Dual-Line Explosion-Proof Rate/Totalizer Pulse Input with Output Loop-Powered Backlight + Loop Output; Powered from Battery and 9-30 VDC         
PD6830-AP0        Dual-Line Explosion-Proof Rate/Totalizer Pulse Input + Backlight; Powered from 9-30 VDC         
PD6830-APA        Dual-Line Explosion-Proof Rate/Totalizer Pulse Input with Backlight + Loop Output; Powered from 9-30 VDC         
PD6830-CTB        Dual-Line Explosion-Proof Rate/Totalizer Pulse Input with Backlight + Loop Output; Powered by Output Loop         
  

Accessories

Model Description  
PDABAT36D        Approved Replacement Battery         
PDA75PLUG        Metal Stopping Plug with Approvals         

 